Festo Контроллер позиционирования CPX-CMAX User Manual

Page 42

Advertising
background image

2. I/O data and sequence control

2−14

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

CPOS

Control byte 2 (CPOS) controls the positioning sequences as
soon as the drive has been enabled.

Control byte 2 (CPOS) ć record select mode

Bit

EN

Description

B0
HALT

ć

Reserved, must be set to 0.
A warning is signaled for logic 1.

B1
START

Start Positio−
ning Task

With a

rising edge the current setpoint values will be transferred and

positioning started.

B2
HOM

Start

Homing

With a

rising edge, homing is started with the set parameters. ReferencĆ

ing is reset.
A fault is signaled with an absolute measuring system.

B3
JOGP

Jog positive

The drive moves at the specified speed in the direction of increasing
actual values, providing the bit is set.

B4
JOGN

Jog negative

The drive moves at the specified speed in the direction of decreasing
actual values, providing the bit is set.
If JOGP and JOGN are set at the same time, the drive moves in the posiĆ
tive direction.

B5
TEACH

Teach Actual
Value

At a

falling edge, the current actual value is transferred into the setpoint

register of the currently addressed record.

B6
CLEAR

ć

Reserved, must be set to 0.
A warning is signaled for logic 1.

B7

ć

ć

Reserved, must be set to 0.
A warning is signaled for logic 1.