Festo Контроллер позиционирования CPX-CMAX User Manual

Page 185

Advertising
background image

4. Faults and diagnostics

4−49

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Example of diagnostic memory entry for error E50

Diagnostic memory data

Value

Byte

Designation

Description

Dec

Hex

Bin

1
2
3
4
5

Days [day]
Hours [h]
Minutes [m]
Seconds [s]
Milliseconds [ms]

Error was reported 22.66 ms after
switching on the power supply (bit 7 in
byte 5 is set if this is the first entry
since Power ON).

0

d

0

d

0

d

22

d

194

d

00

h

00

h

00

h

16

h

C2

h

00000000

b

00000000

b

00000000

b

00010110

b

11000010

b

6

Module code

Module code of the CMAX: 176

176

d

B0

h

10110000

b

7

Module position
[Pos]

In this case, the CMAX is CPX module
No. 2.

2

d

02

h

00000010

b

8

Channel number

Bit 7

6

5 ... 0

Description

1

0

0 ... 0

Error in I channel

128

d

81

h

10000001

b

9

Error number [FN]

CPX error number: 105

105

d

69

h

01101001

b

10

Following channels

Always 0 for the CMAX

0

d

00

h

00000000

b

Tab. 4/20: Example of diagnostic memory entry

Advertising