Festo Контроллер позиционирования CPX-CMAX User Manual

Page 50

Advertising
background image

2. I/O data and sequence control

2−22

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Status byte 3 (SDIR) ć direct mode

Bit

EN

Description

B0
ABS

Absolute /
Relative

= 0: Setpoint value is absolute
= 1: Setpoint value is relative to last setpoint value

B1
COM1

Control Mode
feed back

1

= 0: Position control active
= 1: Force control active

B2
COM2

Control Mode
feed back

2

For position control only (COM1=0):
= 0: Free profile
= 1: Automatic profile

B3
CONT

Continous
tracking mode

Continuous tracking mode acknowledgment (continuous setpoint
specification):
= 0: Continuous tracking mode inactive
= 1: Continuous tracking mode active

B4
VLIM

Velocity (

V−)

Limit reached

For force control only:
= 0: Speed limit not reached
= 1: Speed limit reached

B5
XLIM

Stroke (

X−)

Limit reached

For force control only:
= 1: Stroke limit not reached
= 0: Stroke limit reached, fault is signaled.

B6
FAST

Fast stop

= 0: Exact stop is active
= 1: Fast stop is active, fault is signaled

B7

ć

ć

Reserved (= 0).

The SDIR status byte is the acknowledgement of positioning
mode in direct mode. All bits except for B0 (ABS) and B6
(FAST) are reset at the START and then updated dynamically.