Force control sequence

If Force control" is set as the control mode with a rising edge
at CPOS.START in RCB1 (record set mode) or in control byte
CDIR (direct mode), the CMAX interprets the setpoint specifiĆ
cation as a force setpoint. It activates the force control and
adjusts the value with the set ramp. The RSB/SDIR signalises
the Force control" status accordingly.

1

Path

2

Force

3

Speed

4

Force control until
drive breaks away

5

Feed phase (V

feed

)

6

Force buildup with
force ramp

7

MC

Path/speed/force

1

2

3

4

5

S

lim

F

V

lim

V

feed

Stroke monitoring

Target force

Speed monitoring

6

Time

7

Fig. 3/1:

Force control phases

Force control is done in phases according to Fig. 3/1
(for stroke and speed monitoring, see monitoring functions,
Fig. 3/2):

1. After starting the force control task until the drive moves

(phase

4 , breaking away").

2. Feed phase/prepositioning at speed setpoint until standĆ

still or target force has been reached (phase

5 ).

If the drive does not encounter any counteracting force
after the force task has started, it accelerates until it has
reached the feed speed V

feed

, and then switches to posiĆ

tioning mode and moves in the direction of the target
force until the counteracting force increases and the conĆ
troller switches back to force control.