Festo Контроллер позиционирования CPX-CMAX User Manual

Page 383

Advertising
background image

B. Basic controlling principles

B−41

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

ć

The controller contains appropriate default settings.

ć

During parameter download, the CMAX only checks the
absolute limit values of the parameters. The parameters
maximum setpoint force and tolerance are

not limited

dependent on other project data (cylinder diameter etc.).

ć

In the CMAX the controller limits the setpoint values to
reachable maximum values. In this, the piston surface,
the moving mass and the mounting position are taken
into account. The limited values can be read from the conĆ
troller and displayed in the same way as the limited accelĆ
eration values for position control.

ć

During force control, either the current position or the
current force value in the PLC input data is transmitted.
Switching over is done via PNU 523:08.

ć

If you want Stop to be carried out (CCON.STOP = 0) while
the drive is pushing into a stop under force control, the
system switches from force control to position control and
adopts the current actual position as setpoint position.
Since the drive is at a standstill, the tolerance is reached
immediately, and transition to standstill control occurs.
The force to which the drive controls in this case is speciĆ
fied by the actual force which can range between the last
setpoint force and 0 N. If the drive is to be positioned
force−neutrally after stop, a force record with 0 N should
be executed before setting CCON.STOP = 0.

Advertising