C. Configuration with CPX node

C−13

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

C.1.5

Acyclical parametrisation with DPV1, parameter READ/WRITE

When using the FB13, there are two ways of accessing the
data.

ć

A direct task for reading/writing the module parameters
is possible, but only for modules 0...9 (data record
number (FB52/53) = 5 + 72 + 15*module number)

ć

Generally valid is an indirect task via the command box,
which has the additional advantage of being able to write
the data as of a certain offset. In this way the bytes 0...7
from the startup parametrisation do not have to be overĆ
written (slot = 100 + module number; index = 21)

Further information on acyclical parametrisation can be found
in the P.BE.CPX−FB13−... description

General access via command box

Slot 3: Indexed addressing of the objects

Index

Name

Length
[byte]

Access

Record number (Siemens)

16

Command box

4

r/w

9

17

Read Box

64

r

10

18

Write Box

64

w

11

Command box: Access to CMAX module parameters

Byte

1

2

3

4

Contents

Slot no.

Index module data

Offset data

ć

CMAX

100 + module number

21

8

0