Festo Контроллер позиционирования CPX-CMAX User Manual

Page 382

Advertising
background image

B. Basic controlling principles

B−40

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

The maximum force applied to the piston is referred to as
nominal force F

N

, and it is calculated as follows:

F

N

[N] = A

N

* p

operation

The maximum forces applied to the drive for both direcĆ
tions of movement are calculated as follows: With non−
horizontal mounting position (

α

š 0 for linear drives, refer

to Fig. B/2) they are dependent on direction and mass:

F

max+

[N] = + 0.9 * A

N

* p

operation

ć m

current

* g * sin

α

F

maxć

[N] = ć 0.9 * (A

N

ć A

KS

) * p

operation

ć m

current

* g *

sin

α

This contains the following user data:

p

operation

= supply pressure

A

N

= nominal piston surface
(e.g. DNCI−25−...: A

N

= ģ / 4 * 0.025

2

)

A

KS

= piston rod surface

m

current

= m

current tool mass

+ m

current workpiece mass

α

= mounting position

The values for F

max+

and F

maxć

are calculated in the conĆ

troller. The controller limits the user data to these limit
values and reports a fault if necessary.

Parameter

Unit

FCT default

Minimum

Maximum

Force tolerance

N

10

1

1.000

Force ramp

N/s

1.000

10

10.000

Speed limit value

mm/s

200

10

1)

500

Stroke limit value

mm

50

1

1)

10.000

1)

The speed and stroke limit values can be deactivated for every force record, so entering 0 is not
permissible.

Advertising