Festo Контроллер позиционирования CPX-CMAX User Manual

Page 143

Advertising
background image

4. Faults and diagnostics

4−7

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

4.2.3

Fault level: Classification according to the response to the fault

The fault level is a classification according to the CMAX
response to an identified diagnostic event.

Fault level

Effects on

SCON

1)

SPOS

1)

Sequence control Axis

Fault

Warn

Open

Enabled

MC

Ref

ć

(0)

No fault

ć

ć

ć

ć

ć

ć

W

(2)

Warning

No change

No change

ć

1

ć

ć

ć

ć

F1

(5)

Fault 1

Transition to the
fault status

Stop with stop
ramp

1

ć

0

ć

1

ć

F2

(6)

Fault 2

Transition to the
fault status

Controller disĆ
abled

1

ć

0

0

1

ć

2)

FS (15)

System
error

3)

System fully stopped,
switching on/off required

x

x

x

x

x

x

1)

Status bits status: ć = no effect; 0 = logic 0, 1 = logic 1; x = no updating

2)

Should communication with the measuring system/sensor interface fail, the reference may be lost
(SPOS.REF = 0).

3)

System error FS : Serious error in firmware (No firmware, ...): It may no longer be possible to upĆ
date the I/O data.

Tab. 4/2: Fault levels