A. Notes on commissioning and service

A−19

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

Parameters

Permissible deviations for nominal/actual comparison

Prior to transfer of SN

1)

After transfer of SN

2)

After identification

Cylinder

Type

no deviation

no deviation

no deviation

Nominal/effective
length

3)

5 mm

5 mm

5 mm

Diameter

no deviation

no deviation

no deviation

PR diameter

4)

no deviation

no deviation

no deviation

Measuring system

Type

no deviation

no deviation

no deviation

Nominal length

5 mm

5 mm

5 mm

Serial number

any changes

any changes

5)

any changes

5)

Valve

Type

no deviation

no deviation

no deviation

Serial number

any changes

no deviation

no deviation

1)

Prior to transfer of the serial numbers any changes to the setpoint configuration are permissible if
there is no actual configuration. A complete actual configuration is currently only available when
using the DGCI.

2)

After transfer of the SN or the identification, these tolerances not only apply to variations between
the setpoint values and actual values, but also between old and new setpoint values.

3)

Only a cylinder length to which both actual values are compared is projected.

4)

Piston rod diameter

5)

No deviation permissible with the DGCI.

Tab. A/2: Permissible deviations for nominal/actual comparison

Optimize parameters

Various parameters can still be modified after commissioning
in order to optimize the project. The cylinder length can, for
example, be modified by up to 5.00 mm in order to be able to
move right up to cylinder end position with force control.