2. I/O data and sequence control

2−20

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

CDIR

Control byte 3 (CDIR) is a special control byte for the
operating mode direct mode.

Control byte 3 (CDIR) ć direct mode

Bit

EN

Description

B0
ABS

Absolute /
Relative

= 0: Setpoint is absolute (relative to the project zero point)
= 1: Setpoint value is relative to last setpoint/actual value

1)

B1
COM1

Control Mode 1 = 0: Position control

= 1: Force control

B2
COM2

Control Mode 2 For position control only (COM1=0):

= 0: Free profile: Speed and acceleration are freely specified
= 1: Automatic profile: Speed and accelerations are specified by the

controller

2)

A fault is signaled for logic 1 when force control is active.

B3
CONT

Continous
(Tracking)
Mode

For position control: Activates continuous tracking mode (continuous
setpoint specification):
= 0: Do not activate tracking mode
= 1: Activate tracking mode

B4
VLIM

Speed (

V) Limit

OFF

For force control:
= 0: Activate speed limit
= 1: Deactivate speed limit

B5
XLIM

Stroke (

X−)

Limit OFF

For force control:
= 0: Activate stroke monitoring
= 1: Deactivate stroke monitoring

B6
FAST

Fast stop

Control for reaching the target setpoint value:

3)

= 0: Exact stop
= 1: Fast stop

B7

ć

ć

Reserved, must be set to 0.
A warning is signaled for logic 1.

1)

The setpoint is relative to the last setpoint (if MC) or the actual value (if no MC).
Force tasks following positioning tasks refer to force 0.

2)

Speed and accelerations are selected by the controller according to the identification so that the
target position is reached as quickly as possible without overshooting.

3)

See section 3.1.4. SPOS.MC is only set when the job is completed according to the quality class.
In the event of a fast stop, the standstill monitoring is deactivated.