4 process data, Process data – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 227

Advertising
background image

5. Parameter

5−39

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

5.4.4

Process data

Position values

PNU

PNU: 300

Index: 1 ... 3

Max index: 3

Class: Array

Data type: int32

Values

Unit: Position (index = 1)

Linear drive

Semi−rotary drive

Dimension Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0.01 mm

−1.000.000 1.000.000 0,1

°

−100.000

100.000

Imperial 0.001 in

−393.701

393.701

0,1

°

−100.000

100.000

Index

Value

1

Current actual position of the controller

2

Current setpoint position of the controller

3

Current controller deviation

When force control is active, the current setpoint position is tracked to the actual position.

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.

Force values

PNU

PNU: 301

Index: 1 ... 3

Max index: 3

Class: Array

Data type: int32

Values

Unit: Force (index = 3)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

DimenĆ
sion

Default

Minimum Maximum

SI 1 N

−1.000.000 1.000.000 1 Nm

−1.000.000 1.000.000

Imperial 1 lbf

−224.809

224.809

1 lbf ft

−737.561

737.561

Index

Value

1

Current actual force of the controller

2

Current setpoint force of the controller

3

Current controller deviation

When position control is active, the current setpoint force = 0.

ý

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.