5 i/o data in commissioning mode, I/o data in commissioning mode, Section 2.2.5 – Festo Контроллер позиционирования CPX-CMAX User Manual

Page 51

Advertising
background image

2. I/O data and sequence control

2−23

Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH

2.2.5

I/O data in commissioning mode

I/O data: Commissioning

Data

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Output
data

CCON

CPOS

Function

Param. 1

Parameter 2
(e.g. current workpiece mass)

Input
data

SCON

SPOS

Function

Progress

Primary actual value
(actual position)

Assignment of the control and status bytes (commissioning
mode):

Assignment of the control bytes (commissioning mode)

CCON
Byte 1

B7
OPM2

B6
OPM1

B5
LOCK

B4

ć

B3
RESET

B2
BRAKE

B1
STOP

B0
ENABLE

y

Mode selection

Block softĆ
ware acĆ
cess

ć

Reset
fault

Release
brake

Stop

Enable
drive

CPOS
Byte 2

B7

ć

B6
CLEAR

B5
TEACH

B4
JOGN

B3
JOGP

B2
HOM

B1
START

B0
HALT

y

ć

ć

Teach
value

Jog negaĆ
tive

Jog posiĆ
tive

Start
homing

Start
positionĆ
ing task

ć

Function
Byte 3

The function number selects the starting commissioning operation in commissioning mode.
The value is interpreted as enumeration. The functions are executed with a rising edge at
CPOS.START.
Value

Function

Description

Param. 1

Param. 2

0

Reserved

Not permissible

ć

ć

1

Identification

Execute identification run

= 0

Workpiece mass

2

Movement test

Execute movement test

= 0

= 0

3 to 255 Reserved

Not permissible

ć

When reserved functions are executed, the CMAX signals a corresponding error.

Param. 1
Byte 4

When executing a commissioning operation: Reserved = 0
When teaching: Teach target, see section 3.2.7.
A zero (0=) must be transferred in setpoint value bytes which aren’t used.

Param. 2
Bytes
5 to 8

Only for Identification" commissioning operation: Current workpiece mass in the set system of
units (see section B.1).
A zero (0=) must be transferred in setpoint value bytes which aren’t used.

Advertising