Festo Контроллер позиционирования CPX-CMAX User Manual

Page 242

Advertising
background image

5. Parameter

5−54

Festo P.BE−CPX−CMAX−CONTROL−EN en 0908NH

Permitted stroke during force control

PNU

PNU: 510

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Position (index = 1)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Dimension Default

Minimum

Maximum

SI 0.01 mm

5.000

100

1.000.000 0,1

°

100

10

100.000

Imperial 0.001 in

2.000

39

393.701

0,1

°

100

10

100.000

Maximum permitted stroke with active force control.
With active force control, the actual position relative to the start position must not change by more
than the amount specified in this parameter. In this way you can ensure that, if force control is actiĆ
vated by mistake (Workpiece missing" for example), the axis will not perform an uncontrolled moveĆ
ment.
This parameter is only taken into account during force control, if the CMAX has Operation enabled."
status.
Monitoring can be deactivated by setting the bits RCB1.XLIM or CDIR.XLIM.

o

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

o

After writing, controller recalculation is carried out.

Lower limit setpoint force)

PNU

PNU: 511

Index: 1

Max index: 1

Class: Var

Data type: int32

Values

Unit: Force (index = 3)

Linear drive

Semi−rotary drive

Dimension

Default

Minimum

Maximum

Force control is not permissible with semi−

d

SI 1 N

0

−100.000

0

p

rotary drives.

Imperial 1 lbf

0

−22.481

0

Smallest permitted setpoint value for a force control. A smaller setpoint value leads to a fault or
warning.
If both the smallest and the largest (PNU 512) permissible force setpoint value are set to zero, the
setpoint limits are ignored when executing a force task.

o

The parameter value cannot be changed.

o

Writing permissible only in commissioning/parametrising mode with disabled controller.

o

This parameter can be written by FCT without higher−order controller.

ý

After writing, controller recalculation is carried out.

Advertising