Westermo OS Management Guide

Version 4.17.0-0

24.3.2.4

SNR-Margin Trigger Configuration Example

Note, this setting only applies to units equipped with DSL ports.

Syntax trigger snr-margin

Context

Alarm Configuration

context

Usage Create a SNR-margin trigger, and enter the

Alarm Trigger Configuration

context for this trigger.

Additional settings for SNR-margin triggers are listed below. The only manda-
tory setting is the list of (DSL) ports - no snr-margin alarm events will occur
until (DSL) ports are defined.

❼ Port(s) (mandatory): Define the port or ports this SNR-margin trigger is

associated with.

Note: SNR-margin alarms can only be generated for ports where a con-
nection has been established.

❼ Alarm threshold: As of WeOS v4.17.0 the SNR-margin falling threshold

is set to 3 (dB) by default, and the rising threshold to 6 (dB) by default.

❼ Enable/Disable: By default, the trigger is enabled.
❼ Condition: By default, the alarm condition is set to low. That is, high is

considered normal and low is considered an alarm situation.

❼ Severity: By default, active severity is WARNING and inactive severity

is NOTIFY.

❼ Action: By default, the trigger is mapped to the default action profile

(action 1).

In this example an SNR-margin trigger is created for DSL ports 1/1 and 1/2,
with falling threshold 4 dB and rising threshold 6 dB.