Section 38.3.6, Section 38.3.7, Section 38.3.8 – Westermo RedFox Series User Manual

Page 891

Advertising
background image

Westermo OS Management Guide

Version 4.17.0-0

38.3.6

Setting Software flow control (XON/XOFF)

Syntax [no] xonxoff

Context

Serial Port Configuration

context

Usage Enable/disable software flow control using XON/XOFF

Use ”show xonxoff” to show the software flow control setting (XON/XOFF)
for this serial port.

Default value Disabled (no xonxoff)

38.3.7

Setting Hardware flow control (RTS/CTS)

Syntax [no] rtscts

Context

Serial Port Configuration

context (only applicable when the serial port

is operating in RS-232 mode)

Usage Enable/disable hardware flow control using RTS/CTS.

Use ”show rtscts” to show the hardware flow control setting (RTS/CTS) for
this serial port.

Default value Disabled (no rtscts)

38.3.8

Selecting serial protocol for a serial (combo) port

Syntax [no] type <rs232|rs422|rs485>

Context

Serial Port Configuration

context (Only applicable to ”combo” RS-232/422/485

and RS-422/485 serial ports. )

Usage Select serial protocol to use for a serial (combo) port. Use, e.g., ”type

rs422” to make a port operate in RS-422 mode. ”no type” resets to the
default type (RS-232 for RS-232/422/485 ports and RS-485 for RS-422/485
ports).

Use ”show type” to show whether the serial (combo) port is configured in
RS-232, RS-422, or RS-485 mode. (This is only of major interest for combo
RS-232/422/485 and RS-422/485 serial ports - a ”regular” RS-232” serial
port cannot be set to anything but RS-232.)

➞ 2015 Westermo Teleindustri AB

891

Advertising
This manual is related to the following products: