Westermo OS Management Guide

Version 4.17.0-0

1. Power off the switch and disconnect all Ethernet cables (including copper

and fiber cables) and DSL cables.

2. Connect one pair (or two pairs) of Ethernet ports as described in the table

below. The ports need to be connected directly, i.e., not via a hub or switch.
Use a straight cable - not cross-over cable - when connecting a port pair.

Product/Model

Ethernet Port Pair 1

Ethernet Port Pair 2

Falcon

FDV-206-1D1S

port 1 port 4

port 2 port 3

Lynx

L106/206-F2G

port 3 port 6

port 4 port 5

L110/210

port 3 port 10

port 6 port 7

Lynx-DSS

L105/205-S1

port 1 port 4

port 2 port 3

L106/206-S2

port 1 port 4

port 2 port 3

L108/208-F2G-S2

port 3 port 6

port 4 port 5

RedFox Industrial

All RFI models

port 1/1 port 1/2

Not applicable

RedFox Industrial Rack

All RFIR models

port 1 port 2

Not applicable

RedFox Rail

RFR-12-FB

port X1 port X6

port X2 port X5

Viper

All Viper-12 models

port X1 port X6

port X2 port X5

Wolverine

DDW-142

port 1 port 2

Not applicable

DDW-142-485

port 1 port 2

Not applicable

DDW-225/226

port 2/1 port 2/4

port 2/2 port 2/3

3. Power on the unit.

4. Wait for the unit to start up. Control that the ON LED is flashing red. The

ON LED flashing indicates that the unit is now ready to be reset to factory
default. You now have the choice to go ahead with the factory reset, or to
skip factory reset and boot as normal.

Go ahead with factory reset: Acknowledge that you wish to conduct the

factory reset by unplugging (one of) the Ethernet cable(s). The ON LED
will stop flashing.