Publication 1757-IN510A-EN-P - October 2003

ProcessLogix Server Upgrade Procedures 4-25

a. Enter >mngr< as the default User Name.

b. Enter >mngr1< as the default Password.

c. Enter >localhost< in the Server Name field.

4. Click OK.

5. Click File

Ex por t.

6. Click Br owse to set the Directory Path to C:\Data\ExportDB.

7. Click Select All.

a. Depending on the size of your database, this step may take

several minutes. It is recommended that you do not export
the examples. New examples are provided with R510.0.

b. To deselect an item, hold <Ctrl> and click each item.

c.

Deselect the following Point Names:

example_cascade

example_motor

example_pid

example_scm

pidloop

8. Click Ex por t.

Depending on the size of your database, this step may take
several minutes to several hours.

9. When completed, close the Export Window (if it did not

automatically close).

1 0. Close Control Builder.

1 1 . Document all CPM/CEE names and addresses.


You will need to create new CPMs/CEEs in R510.0, that have the
same names as the R320.0 CPMs/CEEs, prior to importing your
control strategy.