Publication 1757-IN510A-EN-P - October 2003

Operating System Installation Procedures 2-21

8. If necessary, select the I accept this agr eement option and

click

Nex t.

9. Verify the information on the Regional and Language Options

window and click

Nex t.

1 0. Enter the appropriate Name and Organization and click Nex t.

1 1 . Enter your Windows XP Professional Product Key and click

Nex t.

1 2. At the Computer Name and Administrator Password window:

a. Enter the Computer Name.

b. Enter the Administrator password.

c. Confirm the password.

d. Click

Nex t.

1 3. At the Date and Time Settings window:

a. If necessary, adjust the Date and Time settings.

b. Set the appropriate Time Zone for your location.

c. Uncheck the Automatically adjust clock for daylight saving

changes checkbox.

d. Click

Nex t.

IMPORTANT

The computer name cannot contain more than 14
alphanumeric characters and must contain no spaces.
For a ProcessLogix Client, be sure the name does not
end in the letter “A” or “B”. The suggested name is
STNxx, where xx is the Station Number (01-20).

IMPORTANT

Be sure to document the Administrator Password. (It
is required later in the procedure.) The Administrator
Account and password gives a user full access to the
system. Care should be taken to who has access to
this information.

ATTENTION

!

Failure to uncheck the Automatic adjustment for
Daylight Savings Time causes Redundant Systems to
loose “Sync” when the time is automatically
adjusted. Choosing not to automatically adjust the
time allows you to decide when to make the
adjustment (at a time that is not critical to your
process).