Restoring processlogix data, Restoring processlogix data -35 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual

Page 119

Advertising
background image

Publication 1757-IN510A-EN-P - October 2003

ProcessLogix Server Upgrade Procedures 4-35

Restoring ProcessLogix
Data

Each of the following items should be considered before proceeding.

Table 4.J Restoring ProcessLogix Data Considerations

Item

Post-upgrade

Folders and Files

Copy backed up folders and files from the backup Server
directory to c:\Honeywell\Server after the system is
upgraded.
Custom Displays may require modification for use in an
R510.0 system.

Custom Displays

Custom displays may require modification for use in an
R510.0 system. Copy backed up displays from the backup
abstract directory to C:\Honeywell\Client\abstract.

System Displays

You must reapply the changes to the new display after the
upgrade.

Station Menus

You must reapply the changes to the new menus after the
upgrade.

System Acronyms

You must reapply the changes to the new set after the
upgrade.

Scan Periods

You must reapply the periods after the upgrade.

Localization

You must reapply the settings after the upgrade.

Station configuration file

You must reapply the changes to the new station.ini file after
the upgrade.

Station setup file

The new default setup file, default.stn, is configured as
“static Station 1”. If this is not correct, you must make the
appropriate changes via Station’s Setup menu.
Navigate in Knowledge Builder to Server and Client
Configuration Guide

Configuring Stations and

Printers

Setting Up Station for more information.

History archive search path After upgrading, you must specify the history archive search

path using the ProcessLogix Server Control Panel.
Navigate in Knowledge Builder to Server and Client
Configuration Guide

Understanding and Configuring

Points

History Collection and Archiving

History

Archiving for more information.

Custom applications

Custom applications must be re-compiled and re-linked using
an appropriate development environment.
Navigate in Knowledge Builder to Application Development
Guide

About the Development Environment

Compiling, Linking, and Editing for more information.

Quick Builder projects

When opening an old project file with the new version of
Quick Builder, you are prompted to migrate the project file to
the new format.

File dumps

Do not use any file dumps of the pre-upgrade database to
restore the upgraded database.