Publication 1757-IN510A-EN-P - October 2003

ProcessLogix Server Upgrade Procedures 4-27

Scan Periods

Document any specialized scan periods that were used.

You must reapply the periods after the upgrade.

Localization

Localization settings are lost during the upgrade.

You must reapply the settings after the upgrade.

Station
configuration file

C:\Winnt\station.ini
Document any changes that were made to the station.ini file.
Navigate in Knowledge Builder to Server and Client
Configuration Guide

Configuring Stations and Printers

Station.ini for more information.

You must reapply the changes to the new
station.ini file after the upgrade.

Station setup file

C:\Honeywell\client\station\default.stn
Document any changes that were made to the default Station
setup file, default.stn.

The new default setup file, default.stn, is
configured as “Static Station 1”. If this is not
correct, you must make the appropriate changes to
the Connection Properties.
Navigate in Knowledge Builder to Server and
Client Configuration Guide

Configuring

Stations and Printers

Setting Up Station for

more information.

History archive
search path

Document the history archive search path.

After upgrading, you must specify the history
archive search path using the ProcessLogix Server
Control Panel.
Navigate in Knowledge Builder to Server and
Client Configuration Guide

Understanding and

Configuring Points

History Collection and

Archiving

History Archiving for more

information.

Custom applications

Backup any custom applications built for your existing system. Custom applications must be re-compiled and

re-linked using an appropriate development
environment.
Navigate in Knowledge Builder to Application
Development Guide

About the Development

Environment

Compiling, Linking, and Editing

for more information.

Quick Builder
projects

Backup any Quick Builder projects.

When opening an old project file with the new
version of Quick Builder, you are prompted to
migrate the project file to the new format.

File dumps

Do not use any file dumps of the pre-upgrade
database to restore the upgraded database.

Hardware definition
files

If you want to use existing hardware definition (hdwbld) files
to build printers, you must change any instance of the
CYRILLIC keyword to LANGUAGE=CYRILLIC.

Alarms and
messages

Resolve any alarms before starting the upgrade. Alarms and
messages currently in the system cannot be copied across for
the upgrade.

Handover notes

Handover notes are lost during the upgrade. Handover notes
in the system cannot be copied for the upgrade.

Table 4.I Saving Important R320.0 Server Data

Item

Pre-upgrade Requirement

Post-upgrade