Publication 1757-IN510A-EN-P - October 2003

2-8 Operating System Installation Procedures

b. Enter the Administrator password.

c. Confirm the password.

d. Click

Nex t.

1 4. At the Windows 2000 Components window:

a. Uncheck the box for the Internet Information Services (IIS).

Only the Accessories and Utilities, Indexing Service, and
Script Debugger remain checked.

b. Click

Nex t

.

1 5. At the Date and Time Settings window:

a. If necessary, adjust the Date and Time settings.

b. Set the appropriate Time Zone for your location.

c. Uncheck the Automatically adjust clock for daylight saving

changes option.

d. Click

Nex t.

If setup has not found a suitable Network Device, you are
prompted for installing one. Follow the instructions for adding a
manufacturer supplied driver or add the Microsoft Loop Back
adapter.

1 6. Select the Custom Settings option and click Nex t.

IMPORTANT

Be sure to document the Administrator Password. (It
is required later in the procedure.) The Administrator
Account and password gives a user full access to the
system. Care should be taken to who has access to
this information.

TIP

In the next section, you have the ability to add
many services and options during the Server
installation. These components are not required for
the base operation of the ProcessLogix R510.0
Software. If any of these components are needed
for a custom installation, they can be added later
after the installation.

ATTENTION

!

Failure to uncheck the Automatic adjustment for
Daylight Savings Time causes Redundant Systems to
loose “Sync” when the time is automatically
adjusted. Choosing not to automatically adjust the
time allows you to decide when to make the
adjustment (at a time that is not critical to your
process).