Pc naming rules, Pc naming rules -7 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual

Page 27

Advertising
background image

Publication 1757-IN510A-EN-P - October 2003

Operating System Installation Procedures 2-7

Rockwell Automation recommends selecting the “Per Seat”
licensing option.

1 3. At the Computer Name and Administrator Password window:

a. Enter the Computer Name.

IMPORTANT

Microsoft requires that you attain the appropriate
number of Client Access Licenses required for your
system. For ProcessLogix Systems, the total number
of clients includes other ProcessLogix Servers
(Redundant Servers), and ProcessLogix Clients.

When you purchase a ProcessLogix Client License,
a Client Access License for Windows 2000 Server is
included.

IMPORTANT

It is strongly recommended that you name your
Server properly prior to installing ProcessLogix
R510.0 software.

Once the ProcessLogix R510.0 software is installed,
changing the computer name requires a full uninstall
and reinstall of all the ProcessLogix R510.0 software.
Refer to Changing the Computer Name on a
ProcessLogix Server on page 8-16
.

IMPORTANT

PC Naming Rules

The base name cannot contain more than 13
alphanumeric characters and must contain no spaces.
The full computer name cannot contain more than
14 alphanumeric characters. The following naming
conventions are required for given ProcessLogix
system architectures.

For non-redundant Server, be sure the name does
not end in the letter “A” or “B”. The default name is
PLX1.

For redundant Servers, append a letter to the base
name to identify the PC’s function in the system
architecture beginning with the letters A and B for
the primary and secondary Servers, respectively. For
example, use the name PLX1A for the primary Server
(

SERVERA) and PLX1B for the secondary Server

(

SERVERB). (14 Character total: Up to 13 Base plus

A or B)

For a ProcessLogix Client, be sure the name does not
end in the letter “A” or “B”. The suggested name is
STNxx, where xx is the Station Number (01-20).