User interface capacity and performance, User interface capacity and performance -7 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual

Page 247

Advertising
background image

Publication 1757-IN510A-EN-P - October 2003

Performance and Capacity Specifications 11-7

User Interface Capacity and Performance

Table 11.D Operational Display Update Rates

Operation Display Update Rates

Maximum Continuous Display Update Rate

1 sec

Maximum Number of Parameters/Display

300

Typical Field Change to Display Update Time with 100 Parameters Per Display on a Single Station/Server

(Server configured for 1 sec update)

< 2 sec

Typical Display Call Up Time with 100 Parameters on a Single Station/Server

(Call up time is dependent on display complexity; this excludes the first initial call up.)

< 2 sec

Maximum Number of Stations Connected to one Server

20

Maximum Number of Concurrent Users Connected to one Server.

See Table 11.G Server communication NetBIOS session capacity on page 11-9.

Unlimited for Windows 2000
Sever based system

Table 11.E Multi-user CB/FLM Operational Limits

Multi-user CB/FLM Limits

Maximum CB Clients connected to single Server

4

Remote Access Service (RAS) support for Multi-User CB

Not Supported

Dial-up Networking support for Multi-User CB

Not Supported

Minimum continuously available Network Bandwidth required for each multi-user CB Client.

128KB

Maximum Fieldbus Library Manager Clients connected to a single server

1

Advertising