ProcessLogix Server Upgrade Procedures 4-7
d. If necessary, select
Classic Ser ver Secur ity in the Domain
Name drop-down list.
5. Expand Pr ocessLogix Node.
6. Click Admin Tasks.
7. Click Disable Replication.
8. Click OK at the Disabled Database Replication prompt.
9. Close DbAdmin.
Exporting the Database Using Control Builder
Complete these steps on a non-redundant Server or
SERVERB.
1 . If necessary, logon to the system as ps_user.
2. Using Windows Explorer, create the folder C:\Data\ExportDB.
3. Click Star t
⇒ Pr ograms ⇒ Pr ocessLogix Engineering Tools
⇒ Contr ol Builder.
4. In the Login dialog box, make these entries:
a. Enter >mngr< as the User Name.
b. Enter the appropriate Password.
c. Enter >localhost< in the Server Name field.
d. Select
Classic Ser ver Secur ity in the Domain Name
drop-down list.
5. Click OK.
6. Click File
⇒ Export.
7. Click Br owse to set the Directory to C:\Data\ExportDB.
8. Click Select All.
a. Depending on the size of your database, this step may take
several minutes. It is recommended that you do not export
the examples. New examples are provided with R510.0.
b. To deselect an item, hold Ctrl and click each item.