Exporting the Engineering Repository Database

Complete these steps on a non-redundant Server or on

SERVERB.

1 . Logon to the Server as ps_user.

2. Using Windows Explorer, create the folder C:\ExportDB.

3. Click Star t

Pr ograms Pr ocessLogix Engineering Tools

Contr ol Builder.

4. In the Login dialog box, make these entries:

a. Enter >mngr< as the default User Name.

b. Enter the appropriate Password.

c. Enter the appropriate Server name in the Server Name field.

d. Select

Classic Ser ver Secur ity in the Domain Name

drop-down list.

5. Click OK.

6. Click File

Export.

7. Click Br owse to set the Directory to export the data to

C:\ExportDB.

8. Click Select All.

Depending on the size of your database, this step may take
several minutes.

9. Click Ex por t.

Depending on the size of your database, this step may take
several minutes to several hours.

1 0. Close Control Builder.

IMPORTANT

Process systems must export their Engineering
Repository Database at this time before proceeding.

The data that is saved during this step can be stored
on the existing system, but can NOT be contained
within the C:\Honeywell path.

For example, create a directory at the root of C:

(e.g., C:\ExportDB).

If the system is clean (i.e., no configuration applied
yet), this procedure can be skipped.