Publication 1757-IN510A-EN-P - October 2003

Firmware Maintenance Procedures 7-5

Interface module (TC-MUX021) to match the current ProcessLogix
software version before you can download a control strategy.

Firmware Revision Level
Reference

The following table lists the firmware revision levels for listed
components that are current for R510.0 along with the directory
locations for firmware upgrade files.

IMPORTANT

Firmware versions for these modules are not
qualified for backward compatibility. For example, if
you try to use a 1757-PLX52 with a firmware version
that is compatible with R510.0 with a Server running
software version R300.1, the control and operation of
the system is not guaranteed.

ATTENTION

!

This release of ProcessLogix supports only the
firmware versions listed in Table 7.A. When installing
new systems or repairing existing systems, you must
ensure that all modules meet the firmware version
requirements listed in Table 7.A.

Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.

Table 7.A Hardware component firmware revision level reference for R510.0

Component Name

Model Number

Revision Level
for R510.0

Directory

File

Process Controller
Module

1757-PLX52
(redundant-

compliant)

AV 500.1-01.1
BV 500.1-01.1

C:\Honeywell\tps50\system\bin

Cee5.pcm

Cee50.pcm
Cpmboot.pcm

Serial Interface
Module (SIM)

TC-MUX021

AV 500.1-01.1
BV 500.1-01.1

C:\Honeywell\tps50\system\bin

Simboot.pcm

simrex.pcm

Use this base directory path to locate the firmware directories and files for the following modules:

C:\Honeywell\tps50\system\firmware

Redundancy
Module (RM)

1757-SRM

AV 3.29
BV 3.2

\1757-SRM\3_29

99450209.nvs