Publication 1757-IN510A-EN-P - October 2003

ProcessLogix Server Upgrade Procedures 4-37

8. Enter the New Password, Confirm the New Password and click

OK.


The message

Passwor d accepted should appear in the message

zone. If it does not, repeat steps 7 and 8.

If migrating a system with Fieldbus devices, continue with Adding
Saved Device Templates Using Fieldbus Library Manager on page
4-37
. Otherwise skip to Importing the Database Using Control Builder
on page 4-38.

Adding Saved Device Templates Using Fieldbus Library Manager

For a redundant Server pair, complete these steps on

SERVERB only.

1 . Click Star t

Pr ograms Pr ocessLogix Engineering Tools

Fieldbus Library Manager.

2. In the Login dialog box, make these entries:

a. Enter >mngr< as the default User Name.

b. Enter the appropriate password.

c. Select

Classic Ser ver Secur ity in the Domain Name

drop-down list.

3. Click File

Open Device.

4. Browse to your FFDevices backup directory, select a device and

click

OK.

For example: C:\UpgradeData\FFDevices

5. Click File

Save.

6. If necessary, click Yes at the Resolve Load Destination window.

7. Click OK.

8. Click File

Build Device Template Fr om Curr ent

Device.

Do not use the From Existing .DEF files option.

9. Click OK to confirm file addition.

1 0. Repeat Steps 3-9 for each device stored in the FFDevices backup

directory.

1 1 . Close the Fieldbus Library Manager.