4-6 ProcessLogix Server Upgrade Procedures
Preparing for a 
ProcessLogix R400.0 SP2 or 
R500.1 to R510.0 Server 
Upgrade
Exporting the R400.0 SP2 or R500.1 Engineering Repository 
Database
Use the following procedure to export the Engineering Repository 
Database.
Disabling ERDB Replication
This procedure is only required for a redundant Server pair. Complete 
these steps on 
SERVERB only. If you have a non-redundant server,
skip to Exporting the Database Using Control Builder on page 4-7.
1 . Logon to SERVERB as ps_user.
2. Click Star t
⇒ Pr ograms ⇒ Pr ocessLogix Engineering Tools
⇒ DB Admin.
3. Expand DbAdmin.
4. In the Login dialog box make these entries:
a. Enter >mngr< as the default User Name.
b. Enter the appropriate Password.
c. Enter >localhost< in the Server Name field.
ATTENTION
!
All procedures listed in this section should be 
performed with the system(s) Off-Process. Be certain 
that your process is off control before you begin any 
upgrade procedure. This means the 1757-PLX52 
should be in the Idle state.
IMPORTANT
To save Fieldbus device values and CM block 
parameter values, it is recommended to do the 
following:
1 . Upload w ith Contents of your Control Modules.
2. Update to Pr oject, which saves the Monitor
image to the Project image.
This procedure captures the latest configuration 
changes. Otherwise, after re-loading the CMs 
following the ProcessLogix upgrade, changed values 
would be lost.