Firmware Maintenance Procedures 7-3

1 1 . Close the Computer Management window.

1784-PCIC Driver Installation is complete.

Return to the checklist that led you to this task.

1784-PCIC Firmware
Installation

If your 1784-PCIC firmware has not been updated for ProcessLogix
R510.0, this procedure must be followed to use the 1784-PCIC in
R510.0.

Starting Network Tools Application

If this is the

fir st time you have used Network Tools on this PC, refer

to Making First Time Network Tools Settings on page 8-10 and then
continue with the following steps starting with at Step 6.

1 . Click Star t

Run.

2. Enter >ntools -c -u<.

3. Click OK to launch the Network Tools application.

4. Click OK to acknowledge the warning about monitoring

through Control Builder.

5. Click the resume button

to initiate network scan.

Updating the 1784-PCIC Firmware

6. Click the desired PCIC icon under the Desktop tree and wait for

the card details to appear in the Detail pane.

7. Check the firmware revision shown in the Name field.

• If the firmware is 3.7.39, you do not need to update the

firmware.

• If the firmware is not 3.7.39 go to Step 8.

8. Click the firmware button

to initiate the firmware update.

9. Click Yes to acknowledge the Warning prompt.

IMPORTANT

You must have the 1784-PCIC configured in RSLinx.
Refer to Configuring RSLinx Drivers for ControlNet
Supervisory Network on page 3-16 to
configure the
1784-PCIC drivers in RSLinx.