Controller notifications, Controller redundancy, Controller notifications controller redundancy – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual

Page 257

Advertising
background image

Publication 1757-IN510A-EN-P - October 2003

Performance and Capacity Specifications 11-17

Controller Notifications

Controller Redundancy

Table 11.L Controller Notifications Performance

1757-PLX52 and 1757-FIM Controller Notifications Performance

Maximum number of events

(1)

(burst condition)

(1)

Event burst will be throttled to one burst per minute to allow the server to process the previous burst. The

sustained rate may continue between bursts.

50 events

Maximum number of event/second

(1)

(sustained)

2/sec

ATTENTION

!

The Ethernet Modules cannot be used with
Controller Redundancy

Table 11.M Controller Redundancy (50 ms CEE only) Specifications

Controller Redundancy (50 ms CEE only)

Redundancy compliant devices

CNB

1757-PLX52

1757-SRM
1757-BEM

Non-redundancy compliant devices (cannot be introduced in a
redundant controller chassis)

1756 IOM

TC-MUX021

1757-PIM

1757-FIM

SST-PFB-CLX

Controller models supported

1757-PLX52 only

Control Processing Switchover Interruption Time

500 ms

Redundancy Module Cable Medium

Fiber Optic Cable

Redundancy Module Cable Lengths

1, 3, 10, 100 meters

Redundancy Module Slot Width

2 slots

Initial Synchronization Timer (from Sync Start to Completion)

90 sec

Maximum Elapsed Time Between Commanded Switchover and
Completion of Initial Synchronization

120 sec

Maximum Elapsed Time Between Switchover Due to Power
Cycle of the Primary and Completion of Initial Synchronization

150 sec