Publication 1757-IN510A-EN-P - October 2003

4-40 ProcessLogix Server Upgrade Procedures

1 1 . To import the data, enter >sysbld -restore C:\

Honeywell\server\backup\data -y< and press <Enter>.


Depending on the size of your database, this step may take
several minutes.

1 2. To start the ProcessLogix Server enter >hscserver /start /y< and

press <Enter>.

1 3. Close the command prompt.

Upgrading Hardware Component Firmware

1 . Refer to 1784-PCIC Driver Installation on page 7-1 and

1784-PCIC Firmware Installation on page 7-3 to upgrade the
1784-PCIC to the supported driver and firmware revisions.

2. Refer to Loading 1757-PLX52, TC-MUX021, or 1757-FIM Boot

and Personality Images on page 7-9 to

upgr ade the 1757-PLX52

boot and personality images to the current release level.

3. After upgrading the 1757-PLX52, refer to Upgrading Hardware

Component Firmware on page 7-4 to check if other hardware
components require upgrades.

IMPORTANT

Stop! It is mandatory that you check the firmware
revision levels for

ALL ProcessLogix hardware

components after a ProcessLogix software
installation and/or a component addition or
replacement.

Do

not proceed until you have upgr aded the

firmware. Then go to the next section, Backing Up a
ProcessLogix Server Hard Drive to Tape.

ATTENTION

!

If you also upgraded from a non-redundant
1757-PLX52 to a redundant 1757-PLX52, you must
delete the existing CPM and its associated CEE from
the Project tab, reconfigure a new 1757-PLX52 and its
associated CEE, and reassign the components before
you download the CPM to the Controller.