7-14 Firmware Maintenance Procedures

The procedure for updating the firmware in other modules is similar
to the one used for updating a 1784-PCIC card.

1 . Launch the NTOOLS utility (ntools -c -u or ntools -e -u).

refer to Starting Network Tools Application on page 7-8.

2. Click the desired CNB or ENET icon.

3. Select the module to be updated in the chassis graphic.

4. Click the firmware button

and click

Yes to acknowledge

the warning.

5. Select the path to the correct .nvs file.

See Table 7.A on page 7-5.

6. Carefully follow the on-screen prompts to complete the update.

If you have added any new CNB modules to your network, adjust the
Network Update Time (NUT) in the new modules. Refer to Setting
CNB Module NUT Timing on page 7-15. Otherwise,
return to upgrade
or installation procedures as applicable.

ATTENTION

!

Be certain that you select the correct .nvs update file
before you acknowledge any Warning prompt and
initiate a file download to a given module. See
Table 7.A on page 7-5.

Do

not update more than one module of a given

type at a time. If the on-screen prompt includes a
selection for “Update all other identical types in this
controller (only) now”, be certain this selection is
not checked

.