Firmware Maintenance Procedures 7-11

7. To load the boot image to a 1757-PLX52, TC-MUX021, or

1757-FIM, locate the appropriate boot file. See Table 7.C, below.

This example illustrates loading boot image to a 1757-PLX52.

8. Select the appropriate file.

9. Click Open to start the firmware load and click Yes to confirm

the action.

1 0. Wait for the load to complete and the 1757-PLX52, TC-MUX021,

or 1757-FIM module to reboot to its ALIVE status as shown in
the module LED display. The Status field in the lower portion of
the Network Tools window tracks the load progress.

1 1 . Click OK to acknowledge the load completion with no errors.

Table 7.C Boot Image Reference for R510.0

Model Number

Directory

File

1757-PLX52

C:\Honeywell\TPS50\system\bin

cpmboot.pcm

TC-MUX021

C:\Honeywell\TPS50\system\bin

simboot.pcm

1757-FIM

C:\Honeywell\TSP50\system\Firmware\1757-FIM

Fimboot.pcm