Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 195
Publication 1757-IN510A-EN-P - October 2003
Firmware Maintenance Procedures 7-11
7. To load the boot image to a 1757-PLX52, TC-MUX021, or
1757-FIM, locate the appropriate boot file. See Table 7.C, below.
This example illustrates loading boot image to a 1757-PLX52.
8. Select the appropriate file.
9. Click Open to start the firmware load and click Yes to confirm
the action.
1 0. Wait for the load to complete and the 1757-PLX52, TC-MUX021,
or 1757-FIM module to reboot to its ALIVE status as shown in
the module LED display. The Status field in the lower portion of
the Network Tools window tracks the load progress.
1 1 . Click OK to acknowledge the load completion with no errors.
Table 7.C Boot Image Reference for R510.0
Model Number
Directory
File
1757-PLX52
C:\Honeywell\TPS50\system\bin
cpmboot.pcm
TC-MUX021
C:\Honeywell\TPS50\system\bin
simboot.pcm
1757-FIM
C:\Honeywell\TSP50\system\Firmware\1757-FIM
Fimboot.pcm