Publication 1757-IN510A-EN-P - October 2003

4-38 ProcessLogix Server Upgrade Procedures

Importing the Database Using Control Builder

1 . Click Star t

Pr ograms Pr ocessLogix Engineering Tools

Contr ol Builder.

2. In the Login dialog box, make these entries:

a. Enter >mngr< as the default User Name.

b. Enter the appropriate Password.

c. Enter the appropriate Server name in the Server Name field.

d. Select

Classic Ser ver Secur ity in the Domain Name

drop-down list.

3. Click File

Import.

4. Click Br ow se to set the import Directory Path to your Exportdb

backup directory.

For example: C:\R320Data\ExportDB or

C:\UpgradeBackupData\ExportDB.

5. Click Select All.

a. Depending on the size of your database, this step may take

several minutes. It is recommended that you do not import
the examples. New examples are provided with R510.0.

b. To deselect an item, hold Ctrl and click each item.

c. Deselect the following Point Names:

All CEEs

All CPMs (only if importing from R320.0)

example_cascade

example_motor

example_pid

example_scm

pidloop

6. Click Impor t.


Depending on the size of your database, this step may take
several minutes to several hours.

IMPORTANT

If importing from R320.0, you need to recreate your
CPMs prior to importing the control strategies. When
recreating the CPMs and CEEs, make sure that you
use the exact same names as were used in R320.0.

IMPORTANT

Do not import any CEEs. Attempting to import CEEs
from a prior release will cause the import to fail.