Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual

Page 168

Advertising
background image

Publication 1757-IN510A-EN-P - October 2003

6-8 Additional Redundant Server Procedures

9. If you have redundant LANs, modify the file to include the

following entries for dual data links.

>DEL LNK00<

>ADD LNK00 NETWORK_LINK<

>DEL LNK01<

>ADD LNK01 NETWORK_LINK<

The default file definition is for a single network (LAN) data link

1 0. Click File

Save to save your changes to the file.

1 1 . Close Notepad.

1 2. Close Windows Explorer.

1 3. Click Star t

Run.

1 4. Enter >cmd< and click OK to open the DOS window.

1 5. At DOS prompt, enter >cd \Honeywell\server\user< and press

<Enter>.

1 6. Enter >hdwbld redun.hdw< and press <Enter>.

The hdwbld utility reads the text file [redun.hdw] and adds the
hardware definitions to the Server database.

If you are using a dual LAN, be certain that you change the
default redun.hdw file as noted in Step 7 to Step 12.

1 7. Verify that no hardware build errors are listed. If errors are listed,

be sure the Server state is Database Only and retry.

1 8. Enter >exit< and press <Enter> to exit DOS.

IMPORTANT

For information about the required operator actions
for the setup of fast failover, navigate in Knowledge
Builder to Server and Client Configuration Guide

Configuring and Monitoring a Redundant Server
System

Server Redundancy Fast Failover

Configuration topic for HOSTS file and redundant
hardware build details.

Advertising