Synchronizing other files, Upgrading hardware component firmware, Checking control builder operation and logging on – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual

Page 182: Synchronizing other files -22, Upgrading hardware component firmware -22

Advertising
background image

Publication 1757-IN510A-EN-P - October 2003

6-22 Additional Redundant Server Procedures

Synchronizing Other Files

The Primary

SERVERA automatically transfers ProcessLogix Server

database information to the Secondary

SERVERB. This transfer

includes any changes in configuration data, such as points and
displays.

Navigate in Knowledge Builder to Server and Client Configuration
Guide

Configuring and Monitoring a Redundant Server System

Synchronizing Other Files for more information.

If you previously configured the flbkup.def file for an earlier release,
you

MUST re-configure it for R510.0.

Upgrading Hardware
Component Firmware

1 . Refer to Loading 1757-PLX52, TC-MUX021, or 1757-FIM Boot

and Personality Images on page 7-9 to

upgr ade the 1757-PLX52

boot and personality images to the current release level.

2. After upgrading the 1757-PLX52, refer to Upgrading Hardware

Component Firmware on page 7-4 to check if other hardware
components require upgrades.

Checking Control Builder Operation and Logging On

Complete the following general steps to log on and check Control
Builder operation on a ProcessLogix Engineering Workstation.

1 . Click Star t

Pr ograms Pr ocessLogix Engineering Tools

Contr ol Builder.

2. In the Login dialog box, make these entries:

a. Enter >mngr< as the default User Name.

b. Enter the appropriate password.

c. Enter the appropriate Server Name in the Server Name field.

d. Select

Classic Ser ver Secur ity in the Domain Name

drop-down list.

IMPORTANT

Stop! It is mandatory that you check the firmware
revision levels for

ALL ProcessLogix hardware

components after a ProcessLogix software
installation and/or a component addition or
replacement.

Do

not proceed until you have upgr aded the

firmware. Then continue with the next section.

Advertising