Publication 1757-IN510A-EN-P - October 2003

4-28 ProcessLogix Server Upgrade Procedures

Exporting the ProcessLogix Server Database

If you have a Redundant Server pair, complete this procedure on
SERVERA only.

1 . Logon to the R320.0 system as plx_user.

2. Click Star t

Run.

3. Enter >cmd< and click OK to open the DOS window.

4. At the DOS prompt, enter >hscserver /unload /y< and press

<Enter>.

5. Enter the following command:

>xcopy C:\Honeywell\server\data\*.* C:\Data\Server\backup /E<

and press <Enter>.

6. If necessary, enter >D< to specify that backup is a directory.

7. Wait until the C:\ prompt appears and close the DOS window.

Removing the RSLinx Software Activation File

It is possible to transfer your RSLinx Activation codes from the old
system to the new system. To move the activation file from your
R320.0 Server:

1 . Locate the RSLinx Master Disk and insert it into the floppy drive.

2. Click Star t

Run.

ATTENTION

!

Before exporting the ProcessLogix Server Database,
you

MUST exit all ProcessLogix applications and

stop all ProcessLogix services. You must complete
the procedure on page 1-8 of the ProcessLogix
R320.0 Installation and Upgrade Guide, before
continuing.

If you have a redundant server pair, you must
complete this procedure on

SERVERB first. Then

complete the entire procedure again on

SERVERA.