Publication 1757-IN510A-EN-P - October 2003

Additional Redundant Server Procedures 6-17

1 2. Click Cancel at the Unable to connect prompt, if applicable.

1 3. Click Station

Connect to call up the Station Connect dialog

box.

1 4. Select Default and click Edit Connection.

1 5. On the Connection tab, make these entries to have the Station

point to

SERVERA (PLX1 A):

a. In the Server field, enter or

Br ow se to the Primary Server

name,

SERVERA.

b. Select the Station type as

Static Station.

c. Enter >2< as the Static Station Number and click Advanced.

d. Check the

Aux iliar y setup file checkbox.

e. Click

Br owse and navigate to:

C:\Honeywell\Client\Station\defaultb.stn and click

Open.

1 6. Click Save.

1 7. Click Yes to save changes.

1 8. Select Default and click Connect.

1 9. Click Cancel at the Unable to connect prompt, if applicable.

20. If you have redundant LANs, you must repeat Step 1 through

Step 19 to set up files for the second LAN using the name or IP
address of

SERVERA and SERVERB specified in the Hosts file

for the second LAN

.

Navigate in Knowledge Builder to Server and Client
Configuration Guide

Configuring and Monitoring a

Redundant Server System

Configuring Stations for Server

Redundancy

Dual Network Configuration for more

information.

21 . Click Station

Exit.

22. Click Yes to exit Station.

IMPORTANT

You must indicate the full path to the .stn file.