7-16 Firmware Maintenance Procedures

4. Click OK to launch the Network Tools application.

5. Click OK to acknowledge the warning about monitoring

through Control Builder.

6. Click Resume

to initiate network scan.

7. Click any CNB icon under the Desktop tree and wait for the

graphic of the chassis to appear in the Detail pane.

8. In the graphic of your chassis, click the CNB module with the

Network Address selected above.

9. Click Change ControlNet

to call up the Keeper Values

dialog box.

1 0. Confirm that the values listed for the parameters under the

Changes Tab on the dialog box match the following settings and
enter new values, as required.

Be certain to adjust the Number of Repeaters, Cable Length, and
Fiber Optics settings to match your actual system configuration
when they differ from the suggested default values listed below.

• NUT Time: 10000 uS (10 msec.)
• Smax: 1
• UMax: 24
• Number of Repeaters: 0
• Cable Length: 1000 (meters)
• Cable Usage: A+B (for dual media cable configuration) or A

(for single media cable configuration)

• Uncheck My System uses Fiber Optics.

TIP

This may be the only module that appears in the
chassis graphic at this time.

TIP

The values listed below differ for applications that
include a Foundation Fieldbus Linking Device.

If you are including a Foundation Fieldbus Linking
Device in your application, review the CNB
restrictions covered in the Linking Device
Implementation Guide
in Knowledge Builder for
NUT timing data specific to Fieldbus applications