Configuring stations in quick builder (on servera) – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 171

Publication 1757-IN510A-EN-P - October 2003
Additional Redundant Server Procedures 6-11
6. On SERVERB, click
Star t
⇒ Run.
7. Enter >cmd< and click OK to open the DOS window.
8. At the DOS prompt, enter >dual_status< and press <Enter>.
9. The unsynchronized SERVERB data should be similar to this:
1 0. Verify that the data link is available.
Configuring Stations in
Quick Builder (on
SERVERA)
1 . Click Star t
⇒ Pr ograms ⇒ Pr ocessLogix Server ⇒ Quick
Builder.
2. Select the New Pr oject option and click OK.
3. In the Save in drop-down list, select
C:\Honeywell\client\qckbld.
4. Enter >Stations.qdb< in the File name field and click Save.
5. Wait for the Enable Components dialog box to open.
a. Under the System/License Details tab, click the down arrow
and select
Pr ocessLogix - R500 from the Server drop-down
list.
b. Select the
Enable Components tab.
c. Click
Unselect All, then check Static Station and Ser ver.
d. Click
OK.
e. A Quick Builder prompt stating that you have not selected
any devices appears. Click
OK to continue.