Publication 1757-IN510A-EN-P - October 2003

Performance and Capacity Specifications 11-23

FIM Performance Limits

The FIM is a complex device interfacing the high-speed ProcessLogix
internal networks to the 31.25 Kbps FF H1 links. It uses an advanced
caching scheme to maintain quick response to reasonably fresh values
and maintains communications with the multiple FF devices as time
permits in the prioritized scheme of the Link Schedule based on FF
specification requirements. This table describes limits of performance
through the FIM.

The FIM cache (one for both links) holds 800 items. An item can be:

• A simple parameter
• A structured parameter
• An arrayed parameter

Quality of service is based on priorities (highest to lowest).

• Incoming H1 Subscriptions and outgoing H1 Publications, per

LAS

• H1 Alerts
• H1 Writes
• New H1 reads (and re-written parameters)
• H1 Re-reads to refresh the cache

Table 11.U 1757-FIM Performance Limits

FIM Performance Limits

Per FIM

Per Link

Per Device

Burst

Sustained

Burst

Sustained

Burst

Sustained

H1 Link Publication Rate (parameters/second, pps)

---

32

(1)

---

16

(1)

---

16

(1)

Client-Server Store Rate

(1)

(pps) [excludes publications from

ProcessLogix function blocks]

40

10

(5)

20

5

(5)

4

1

(5)

Max number of slow history points.

(1)

---

40

---

20

(6)

---

20

(6)

Max number of read-activities per second.

(1)

• A read-activity includes any or all of a block view list parameters or

a single non-viewed parameter.

• Includes all users such as slow history, SCM connections to

non-published parameters, Excel or OPC reads of non-published
parameters, etc.

10

10

5

5

2

2

Maximum number of parameters read per second.

(1)(2)

• Includes all users such as CM connections to non-output

parameters (e.g. tuning constants or limits),

• SCM connections to non-published parameters, Excel or OPC reads

of non-published parameters, etc.

80

80

40

40

16

16

Maximum Alert Rate per second. (Alarm and Return-to-Normal
reports)

(1)(3)

50

2

50

2

2

1

Maximum Number of Devices

32

(4)

16

---

(1)

Assumes

≥ 50% of link schedule is usable for client-server messaging.

(2)

Assumes all parameters read are in view lists and the average number of parameters read and used per view is 8.