Supplementary Procedures 8-25

procedure to confirm that any client reference the correct
non-redundant server or computer name or IP address.

Setting up a ProcessLogix Client with Redundant Servers

If ProcessLogix Client is networked to redundant Servers, refer
to ProcessLogix Client Supported Installations on page 1-4
.

Adding 1757-PLX52
Controller Redundancy to
R510.0 Non-Redundant
1757-PLX52 Controller
Configurations

Deleting a Non-Redundant 1757-PLX52 and Unassigning its
Contents

Complete the following steps to save your existing database and
delete it from the existing non-redundant 1757-PLX52 Controller.

1 . Start Control Builder.

2. Close any open Control Module and/or Sequential Control

Module.

3. In Monitoring tab, expand the non-redundant CPM to display

the CEE folder icon.

4. Click the CEE folder icon.

5. Click Tools

Upload with Contents to upload the existing

controller database.

6. Click Continue.

This may take considerable time to complete, depending on the
amount of CM/SCMs (and their number of FBs and/or number
of Steps/Transitions) currently assigned to this CEE.

7. Click the CEE folder icon.

8. Click Tools

Update with Contents (to Project) to save the

existing controller database.

ATTENTION

!

Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.