Publication 1757-IN510A-EN-P - October 2003

7-8 Firmware Maintenance Procedures

Important Usage Considerations

Be certain that you keep the following considerations in mind when
you are doing a firmware update.

• If you are updating a 1784-PCIC card, your PC will be blind to

all modules.

• If you get a “Warning: Use Extreme Care” dialog box during the

course of an update, confirm that the correct .nvs file is selected.
See Table 7.A on page 7-5.

• Be certain that you carefully read all the dialog boxes presented

during the course of a given firmware update.

Starting Network Tools Application

If this is the

fir st time you have used Network Tools on this PC, refer

to Making First Time Network Tools Settings on page 8-10 and then
continue with the following steps, starting at Step 5.

1 . Click Star t

Run.

a. For ControlNet Supervisory Networks, enter >ntools -c -u<.

b. For Ethernet Supervisory Networks, enter >ntools -e -u<.

2. Click OK to launch the Network Tools application.

3. Click OK to acknowledge the warning about monitoring

through Control Builder.

4. Click the resume button

to initiate network scan.