ProcessLogix Server Upgrade Procedures 4-9

7. Enter >xcopy C:\Honeywell\TPS50\System\ER\Release\*.*

C:\Data\FFdevices /E<

and press <Enter>.

8. If prompted, enter >A< to specify all files and folders.

9. Close the DOS window.

Saving Important R400.0 SP2 or R500.1 Server Data

Each of the following items should be completed on an R400.0 SP2 or
R500.1 Server before proceeding.

IMPORTANT

Redundant Pr ocessLogix Systems

All steps need to be performed on both the Primary
(

SERVERA) and Backup (SERVERB) ProcessLogix

Servers.

If you have a redundant Server pair, you must
complete this procedure on

SERVERB first. Then

complete the entire procedure again on

SERVERA.

ATTENTION

!

Before saving ProcessLogix data, you

MUST exit all

ProcessLogix applications and stop all ProcessLogix
services. You must complete the procedure in
Stopping ProcessLogix Applications and Services on
page 8-1 be
fore continuing.

If you have a redundant Server pair, you must
complete this procedure on

SERVERB first. Then

complete the entire procedure again on

SERVERA.