8-28 Supplementary Procedures

Creating a Redundant 1757-PLX52

1 . Create redundant CPMs

Navigate in Knowledge Builder to Control Building Guide

Hardware Module Creation

Creating a Control Processor

Module for more information about configuring a redundant
1757-PLX52 in Control Builder.

2. Create redundancy modules.

Navigate in Knowledge Builder to Control Building Guide

Hardware Module Creation

Creating Redundancy Modules

for more information about configuring 1757-SRMs in Control
Builder.

3. Once the redundant CPM is created in the Project tab, re-assign

the modules unassigned from the previous non-redundant CPM
to the CEE associated with the new redundant CPM.

Navigate in Knowledge Builder to Control Building Guide

Control Module Creation

Assigning the CM and IOMs to the

CEE for more information.

4. Load the primary and secondary CPMs and RMs to the

Controllers.

Navigate in Knowledge Builder to Control Building Guide

Control Strategy Loading

Loading Objects to the CPM for more

information.

This completes the upgrade to a Redundant Chassis Pair.