Page 230

Publication 1757-IN510A-EN-P - October 2003
8-28 Supplementary Procedures
Creating a Redundant 1757-PLX52
1 . Create redundant CPMs
Navigate in Knowledge Builder to Control Building Guide
⇒
Hardware Module Creation
⇒
Creating a Control Processor
Module for more information about configuring a redundant
1757-PLX52 in Control Builder.
2. Create redundancy modules.
Navigate in Knowledge Builder to Control Building Guide
⇒
Hardware Module Creation
⇒
Creating Redundancy Modules
for more information about configuring 1757-SRMs in Control
Builder.
3. Once the redundant CPM is created in the Project tab, re-assign
the modules unassigned from the previous non-redundant CPM
to the CEE associated with the new redundant CPM.
Navigate in Knowledge Builder to Control Building Guide
⇒
Control Module Creation
⇒
Assigning the CM and IOMs to the
CEE for more information.
4. Load the primary and secondary CPMs and RMs to the
Controllers.
Navigate in Knowledge Builder to Control Building Guide
⇒
Control Strategy Loading
⇒
Loading Objects to the CPM for more
information.
This completes the upgrade to a Redundant Chassis Pair.