11-22 Performance and Capacity Specifications

PROFIBUS DP Capacity and Topology Specifications

The following PROFIBUS specifications are independent of the
interface to ProcessLogix:

• PROFIBUS DP supports a maximum of 126 station addresses,

including, masters, slaves and active repeaters.

• The maximum number of entries in the PBIM configuration

table is 100.

Table 11.T Profibus Capacity/Topology Specifications

PFB Module and PROFIBUS Block Specifications

Note: The PROFIBUS interface module hardware component is the SST-PFB-CLX, and is referred to herein as the PFB Module. This device
acts as the “master” on the PROFIBUS-DP network. Each PFB module is represented as a block in the CEE, which is referred to as the
PROFIBUS Interface Module Block (PBIM).

PROFIBUS Communication Profiles Supported

DP (only)

PROFIBUS Baud Rates Supported

12 MBps, 6 MBps, 3 MBps, 1.5 MBps, 500 KBps, 187.5 KBps,
93.75 KBps, 19.2 KBps, 9.6 KBps,

Support for Multi-Master Configurations

Yes

Support for PROFIBUS Slave Diagnostics

No

Valid PROFIBUS Station address range

0 - 125

Maximum number of modules per PBIM block (identified by a unique
station/module number combination)

100

Maximum Input Data Size per PFB Module

(all slave stations)

496 bytes
(valid range = 4-499)

Maximum Output Data Size per PFB Module

(all slave stations)

492 bytes
(valid range = 4-495)

PROFIBUS Device Profiles Supported

(with custom function blocks)

PROFIDRIVE, Encoder

Devices supported with custom function blocks

Siemens Simatic

®

ET200M I/O, Siemens Simocode 3UF5 Motor Protection and
Control Unit

Data types supported by the “Generic” PROFIBUS Channel Blocks

(1)

Single bit (Discrete),
8 bit signed/unsigned integer,
16 bit signed/unsigned integer,
32 bit signed integer

(1)

The “generic” function blocks are capable of communicating with various PROFIBUS devices. The data types required/supplied by the device are a consideration in the

determination of whether or not a specific device can be used with these blocks.