4-8 ProcessLogix Server Upgrade Procedures

c. Deselect the following Point Names:

example_cascade

example_motor

example_pid

example_scm

pidloop

8. Click Ex por t.

Depending on the size of your database, this step may take
several minutes to several hours.

9. When completed, close the Export Window (if it did not

automatically close).

1 0. Close Control Builder.

Saving Fieldbus Device Definition Files

This procedure is required if migrating a system containing Fieldbus
devices. Complete these steps on a non-redundant Server or
SERVERB. If you do not have Fieldbus devices connected to your
ProcessLogix system, skip to Saving Important R400.0 SP2 or R500.1
Server Data on page 4-9
.

1 . If necessary, logon to the system as ps_user.

2. Using Windows Explorer, create the folder C:\Data\FFdevices.

3. Click Star t

Run.

4. Enter >cmd< and click OK to open the DOS window.

5. At the C:\ prompt, enter

>xcopy C:\Honeywell\TPS50\

System\ER\FFdevices\*.* C:\Data\FFdevices /E<

and press <Enter>.

6. If prompted, enter >A< to specify all files and folders.