2–71

Command Word/Bit Descriptions

Publication 1771-6.5.88 – July 1997

MCC

MCC27

Clamp Position Minimum Software Travel Limit [13] The module continuously compares real-time clamp position against this entry.
The module sets alarm status bit SYS07-B02 and forces all of its outputs to zero when executing a clamp close profile and clamp
position is less than or equals this entry. A zero entry inhibits SYS07-B02.

MCC28

Clamp Position Maximum Software Travel Limit[13] The module continuously compares real-time clamp position against this entry.
the module sets alarm status bit SYS07-B03 and forces all of its outputs to zero when executing a clamp open profile and clamp
position equals or exceeds this entry. A zero entry inhibits SYS07-B03.

MCC29

Clamp Software Travel Limit Alarm Deadband [17] After sensing a clamp overtravel and latching alarm status bit SYS07-B02 or
SYS07-B03, the module will not unlatch bit until real-time clamp position is inside the overtravel setpoint by an incremental length
equal to this entry. This incremental position will be added to MCC27 in order to determine the clamp position required to unlatch
SYS07-B02. This incremental position will be subtracted from MCC28 in order to determine the clamp position required to unlatch
SYS07-B03.

MCC30

Clamp Position Transducer Digital Filter [23] A non-zero entry forces the module to filter the input before using the result for all
clamp position calculations. Use this parameter to soften the input signal from a linear potentiometer.

Clamp Pressure Transducer Configuration

The module accesses data in MCC31-MCC36 if bit patterns in
MCC02 and MCC03 indicate that the module is connected to a
clamp pressure sensor.

Word

Description

MCC31

Minimum Clamp Pressure [02]

MCC32

Maximum Clamp Pressure [02]

MCC33

Analog Signal at Minimum Clamp Pressure [24]

MCC34

Analog Signal at Maximum Clamp Pressure [24]

MCC35

High Clamp Pressure Alarm Setpoint [02] The module continuously compares real-time clamp pressure against this entry. and sets
alarm status bit SYS05-B01 when clamp pressure equals or exceeds this entry. A zero entry inhibits SYS05-B01.

MCC36

Clamp Pressure Alarm Time Delay [23] Total time the module must monitor a continuous clamp pressure in excess of the non-
zero entry in all clamp pressure alarm setpoints before setting the associated alarm status bit. Setpoint/bit pairs affected are:

Setpoint

Alarm Status Bit

MCC35

SYS05-B01

JGC07

SYS05-B10

FCC57

SYS05-B12

SCC57

SYS05-B13

TCC57

SYS05-B14

LPC57

SYS05-B15

FOC57

SYS06-B09

SOC57

SYS06-B10

TOC57

SYS06-B11

OSC57

SYS06-B12

Use a non-zero entry in this word to filter out clamp pressure spikes of short enough duration to avoid nuisance alarms.

Ejector Position Transducer Configuration

The module accesses data in MCC37-MCC44 if bit patterns in
MCC02 and MCC03 indicate that the module is connected to an
ejector position sensor.

Word

Description

MCC37

Minimum Ejector Position [15]

MCC38

Maximum Ejector Position [15]

MCC39

Analog Signal at Minimum Ejector Position [24]

MCC40

Analog Signal at Maximum Ejector Position [24]

MCC41

Ejector Position Minimum Software Travel Limit [15] The module continuously compares real-time ejector position against this entry.
The module sets alarm status bit SYS07-B04 and forces all of its outputs to zero when executing an ejector retract profile and ejector
position is less than or equals this entry. A zero entry inhibits SYS07-B04.