Page 139

Advertising
background image

2–73

Command Word/Bit Descriptions

Publication 1771-6.5.88 – July 1997

MCC

Cavity (or System) Pressure Transducer Configuration

The module accesses data in MCC57-MCC62 if bit patterns in MCC02
and MCC03 indicate that the module is connected to a cavity (or
system) pressure sensor. The data will refer to a system pressure sensor
at input #2 only if MCC02-B03, -B04, and -B05 are all SET.

Word

Description

MCC57

Minimum Cavity (or System) Pressure [04] or [01]

MCC58

Maximum Cavity (or System) Pressure [04] or [01]

MCC59

Analog Signal at Minimum Cavity (or System) Pressure [24]

MCC60

Analog Signal at Maximum Cavity (or System) Pressure [24]

MCC61

High Cavity (or System) Pressure Alarm Setpoint [04] or [01] The module continuously compares real-time cavity (or system) pressure
against this entry. The module sets alarm status bit SYS05-B04 when cavity (or system) pressure equals or exceeds this entry. A zero
entry inhibits SYS05-B04.

MCC62

High Cavity (or System) Pressure Alarm Time Delay [23] Total time the module must monitor a continuous cavity (or system) pressure
in excess of the non-zero entry in all cavity (or system) pressure alarm setpoints before setting the associated alarm status bit.
If bit patterns in MCC02 and MCC03 indicate that the module is connected to a cavity pressure sensor, setpoint/bit pairs affected are:

Setpoint

Alarm Status Bit

MCC61

SYS05-B04

INC58

SYS06-B01

PKC58

SYS06-B03

HDC58

SYS06-B05

If bit patterns in MCC02 and MCC03 indicate that the module is connected to a system pressure sensor, setpoint/bit pairs affected are:

Setpoint

Alarm Status Bit

MCC61

SYS05-B04

JGC06

SYS05-B09

JGC07

SYS05-B10

JGC08

SYS05-B11

FCC57

SYS05-B12

SCC57

SYS05-B13

TCC57

SYS05-B14

LPC57

SYS05-B15

INC57

SYS06-B00

PKC57

SYS06-B02

HDC57

SYS06-B04

PRC57

SYS06-B06

PLC57

SYS06-B07

PSC57

SYS06-B08

FOC57

SYS06-B09

SOC57

SYS06-B10

TOC57

SYS06-B11

OSC57

SYS06-B12

EAC57

SYS06-B13

Use a non-zero entry in this word to filter out cavity (or system) pressure spikes of short enough duration to avoid nuisance alarms.

MCC63

Reserved

MCC64

Number of Input Samples for Loss-of-sensor Alarms [29] Range of 0-200. The module monitors sensor inputs for out-of-range
signals. To avoid nuisance alarms caused by electrical noise, enter a non-zero value. When the module detects a number of
consecutive

out-of-range input scans (consecutive loss-of-sensor samples) equal to or greater than this value, it sets the

loss-of-sensor alarm. Setting to zero gives no protection against nuisance alarms.