Rockwell Automation 1771-QDC PLASTIC MOLD.MODULE User Manual

Page 78

Advertising
background image

2–12

Command Word/Bit Descriptions

Publication 1771-6.5.88 – July 1997

Notes: 1. For [ ] engineering units, see page 3.

2. When using the Inject/Clamp/Eject mode, all pressure readings are system pressure at input 2, except where noted.

Word

Description

CPC34

Segment 9 Pressure Setpoint [02]
if:

then the module:

you select Press/Pos profile execution

controls clamp close pressure to this setpoint from the clamp position CPC32 until clamp
position reaches the larger of CPC35 or CPC61

CPC35

End of Segment 9 Position Setpoint [14]

Clamp Low Pressure Close Profile Setpoints

Word

Description

CPC36

Reserved

CPC37

Segment 1 Pressure Setpoint [02]
The module controls clamp close pressure to this setpoint after starting the Clamp Low Pressure Close Profile until clamp position
reaches the larger of CPC38 or CPC62.

CPC38

End of Segment 1 Position Setpoint [14]

CPC39

Reserved

CPC40

Segment 2 Pressure Setpoint [02]
The module controls clamp close pressure to this setpoint from the clamp position CPC38 until clamp position reaches CPC62.

CPC41 -60

Open

Critical Process Setpoints

Word

Description

CPC61

Start Clamp Low Pressure Close Position Setpoint [14]
The module uses this clamp position (overrun bit) as protection against running a Clamp Close Profile into the Mold Protection Zone.

if:

then the module:

this position is reached while the module is

immediately terminates the ongoing profile and checks state of CPC03-B11

executing any of the first three Clamp Close Profiles

RESET

immediately begins the Clamp Low Pressure Close Profile

SET

sets its outputs to zero

clamp position is less than or equal to this entry

sets master status bit SYS03-B00

it reaches the Mold Protection Zone while executing

sets alarm status bit SYS07-B06

one of the first three Clamp Close Profiles

CPC62

Mold Safe Position Setpoint (Mold Parting Line Touch) [14] This entry is the clamp position when the mold parting line mates

. The

module uses this clamp position as the End of Low-Pressure-Close position setpoint.
if:

then the module:

this position is reached while module is executing

immediately terminates the Clamp Low Pressure Close Profile and sets its

the Clamp Low Pressure Close Profile

outputs to LPC33 - LPC40

clamp position is less than or equal to this entry

sets master status bit SYS03-B01

CPC63

Tonnage Complete Pressure Setpoint [02]
if:

then the module:

clamp position is less than or equal to CPC62

compares real-time clamp pressure against this entry

clamp pressure equals or exceeds this entry when

sets master status bit SYS03-B02

the clamp position is less than or equal to CPC62

CPC64

Open